AJP Asia Intelligence Agency

Collapse at Ulsan Power Plant Claims Seven Lives Due to Structural Miscalculations


The collapse at the Ulsan Power Plant last November, which resulted in the deaths of seven workers, was caused by excessive cutting of columns during demolition work and miscalculations of the structure's load. The actual thickness of the columns was 15mm, but during the structural review, it was incorrectly applied as 24mm, indicating a combination of foundational data errors and inadequate safety assessments.

On October 30, the Ministry of Land, Infrastructure and Transport released the findings of the investigation by the Ulsan Power Plant demolition accident investigation committee. The incident occurred on November 6 at the Ulsan Power Plant during the demolition of Units 4 to 6, specifically during the pre-weakening work on Boiler Tower No. 5, resulting in seven fatalities and two injuries.

The investigation revealed that the accident began during the pre-weakening work, where columns and beams were cut before blasting. The columns were cut beyond their load-bearing limits, leading to local buckling and subsequent chain collapse of the entire structure.

The foundational data used in the structural review was also found to be incorrect. The actual boiler tower had a design where the thickness of the columns decreased as the height increased, but only one measurement from the ground level was applied to the entire upper structure. The actual thickness of the steel plates at the initial collapse point, between 26.2m and 27.2m high, was 15mm, while the structural review used 24mm. Additionally, the weight of the structure was calculated to be 3,005.8 tons, which is 520 tons less than the actual weight of 3,525.8 tons.

Safety assessments were also deemed insufficient. The possibility of local buckling due to the remaining columns being unable to bear the load was not considered, nor was there any safety margin to account for deformation of aging structures or damage during work. The investigation committee conducted a detailed structural analysis reflecting the actual dimensions and weight of the structure, predicting that local buckling would occur at the point where the collapse began.

The investigation also confirmed management deficiencies by both the construction company and the client. The main contractor relied on the judgment of a specialized company for the weakening and blasting work without adequately verifying the consistency between the final construction details and site conditions. The client was found to have inadequately managed the work of participating entities while supervising the project directly without a separate construction project manager.

To prevent future incidents, the investigation committee proposed strengthening site inspections for demolition work, establishing technical standards, enhancing design and construction management for high-risk demolition projects, and expanding client responsibilities. Lee Kyung-gu, the committee chair, stated, "We hope the results of the accident investigation will help prevent similar incidents," adding that a final report will be submitted to the Ministry of Land in November.

The Ministry plans to develop improvement measures for demolition work based on the findings of this investigation and the investigation results of the SeoSeoMun High School demolition accident. Additionally, the ministry intends to notify relevant agencies to facilitate administrative actions and investigations regarding any legal violations.